- Management
- Ethernet
- Networking Interface
- (1) 100/10 MbE port for network connection(2) GbE ports for surge in/out
- Power
- (1) OVC II AC in: NEMA 5‑15P, 1.8 m (5.9 ft) non-removable power cord(4) Battery backup/surge protection: NEMA 5‑15R(4) Surge protection: NEMA 5‑15ROutlets are not individually resettable
- Capacity
- 1,440VA/1,000W
- Type
- Line interactive
- Input Voltage Range
- 89–145V AC
- Power Method
- (1) TN system, 120V AC, 12A Max., 50/60 Hz
- Nominal Input Voltage
- 120V AC
- Output Voltage
- 120V AC
- Frequency Range
- AC mode: 50/60 Hz ±5 Hz (Auto sensing)Battery mode: 60 Hz ±1 Hz
- AC Voltage Regulation
- ±10% (Battery mode)
- Transfer Time
- 6 ms typical; 10 ms max. (Battery mode)
- Wave Form
- Simulated sine wave (Battery mode)
- Battery Type
- (2) Lead Acid 12V, 9Ah
- Runtime
- Full load: 2.3 minHalf load: 8 min
- Battery Charging Time
- 6-8 hours recovery to 90% capacity
- Overload at On-Line Mode
- 110% 5 min go to fault120% go to fault immediately
- Overload at Battery Mode
- 110% shutdown in 5 sec120% shutdown immediately
- Short Circuit Protection at On-Line Mode
- Breaker, 250V AC, 15A
- Output Short-Circuit Current
- Ipeak 348.0AIrms 115.1A
- Buttons
- (1) Power(1) Factory reset
- LEDs
-
- Status
- Off: device not turned onFlashing white: initializing / factory defaultSteady white: waiting for adoptionSteady blue: device adoption and workingFlashing blue: battery modeAlternating white/blue: firmware upgradingRapid flashing blue: locateSteady red: warningFlashing red: low battery
- Operating Altitude
- 3,000 m (1.9 mi)
- Operating Environment
- Pollution Degree 2
- Ambient Storage Temperature
- -20 to 50° C (-4 to 122° F)
- Ambient Operating Temperature
- 0 to 40° C (32 to 104° F)
- Ambient Operating Humidity
- 0 to 95% noncondensing
- Certifications
- FCC, IC, UL 1778, CSA C22.2 No. 107.3